Front of card
Back of card
Furnish New Battery Exide Battery LFP UPS Data Center 2p6x20s 76 5AH 6+6Mods Rack M8
Technology: Pb_VRLA_AGM.pngFurnish New Battery Exide Battery LFP UPS Data Center 2p6x20s 76 5AH 6+6Mods Rack M8
$9,920.80
Material Value Cost Due from Customer.
Furnish New Battery Exide Battery LFP UPS Data Center 2p6x20s 76 5AH 6+6Mods Rack M8
| Battery Model | Exide Battery LFP UPS Data Center 2p6x20s 76 5AH 6+6Mods Rack M8 |
|---|---|
| Adjustment | 1 |
| AH Per String | 139.3509449 |
| AH Per String Rating | 8 hr @ 2.7 VPC |
| Cells Per Unit | 384 |
| Nominal VPC | 3.2 |
| Model KWH | 171 |
| Charge VPC | 3.75 (Min: 3.65, Max: 3.75) |
| Discharge VPC | Min: 2.5, Max: 3.05 |
| Operational Temp Comp | -0.003 V/°C/cell |
| Cycle Temp Comp | -0.004 V/°C/cell |
| Discharge Temp Range | -20°C to 55°C |
| Charge Temp Range | -20°C to 55°C |
| ISC Amps | 0 |
| Internal Resistance | 0 Ohms |
| Dimensions (L x W x H) | 33.464585 x 23.62206 x 78.7402 in |
| Weight | 1984.158 lbs |
| Number of Posts | 1 |
| Terminal Bolt Diameter | 0 in (Post mm) |
| Torque (Initial / Maintenance) | 0 / 0 in-lbs |
| Container | V0 |
| Terminal | Post |
| FOB | T |
| Max Continuous Discharge | 902.3827836 Amps |
| Max Charge Amps | 270.7148351 Amps |
| Max In Series / Parallel | 0 / 0 |
| Watts Per Cell (15min 1.67) | 1429 |
| Watts Per Cell Rating | 15 min @ 2.6 VPC |
| Weight of Electrolyte | 0 lbs |