Furnish New Battery Leoch Battery LHR Series LHR12800W V0 M8
Technology: Lead_Acid_Over120lbsFurnish New Battery Leoch Battery LHR Series LHR12800W V0 M8
$1,253.49
Furnish New Battery Leoch Battery LHR Series LHR12800W V0 M8
| Battery Model | Leoch Battery LHR Series LHR12800W V0 M8 |
|---|---|
| Adjustment | 1 |
| AH Per String | 192 |
| AH Per String Rating | 8 hr @ 1.75 VPC |
| Cells Per Unit | 6 |
| Nominal VPC | 2 |
| Model KWH | 2 |
| Charge VPC | 2.4 (Min: 2.4, Max: 2.4) |
| Discharge VPC | Min: 1.6, Max: 1.9 |
| Operational Temp Comp | -0.003 V/°C/cell |
| Cycle Temp Comp | -0.004 V/°C/cell |
| Discharge Temp Range | -20°C to 55°C |
| Charge Temp Range | -20°C to 55°C |
| ISC Amps | 6772 |
| Internal Resistance | 0.0026 Ohms |
| Dimensions (L x W x H) | 20.6 x 9.45 x 8.82 in |
| Weight | 151.5 lbs |
| Number of Posts | 1 |
| Terminal Bolt Diameter | 0.3149 in (M8 mm) |
| Torque (Initial / Maintenance) | 110 / 125 in-lbs |
| Container | V0 |
| Terminal | M8 |
| FOB | T |
| Max Continuous Discharge | 2050 Amps |
| Max Charge Amps | 51.25 Amps |
| Max In Series / Parallel | 0 / 0 |
| Watts Per Cell (15min 1.67) | 742 |
| Watts Per Cell Rating | 15 min @ 1.67 VPC |
| Weight of Electrolyte | 33.33 lbs |